Conductor gallop is the high-amplitude, low-frequency oscillation of overhead power lines due to wind. The movement of the wires occurs most commonly in the vertical plane, although horizontal or rotational motion is also possible. The natural frequency mode tends to be around 1 Hz, leading the often graceful periodic motion to also be known as conductor dancing. The oscillations can exhibit amplitudes in excess of a metre, and the displacement is sometimes sufficient for the phase conductors to infringe operating clearances (coming too close to other objects), and causing flashover. The forceful motion also adds significantly to the loading stress on insulators and electricity pylons, raising the risk of mechanical failure of either.
The mechanisms that initiate gallop are not always clear, though it is thought to be often caused by asymmetric conductor aerodynamics due to ice build up on one side of a wire. The crescent of encrusted ice approximates an aerofoil, altering the normally round profile of the wire and increasing the tendency to oscillate.